A GPU compute site. Power on the ground, buildout ahead.

2.45 MW is energized to the building today, with a path to 6 MW. Cooling and electrical step-down are the remaining buildout scope. Offered for sale or lease, single-tenant or multi-tenant.

2.45 MW LIVE PATH TO 6 MW 3 PODS · 72 CABINETS PACIFIC POWER GRID
2.45 MW
Contracted power, live
6 MW
Expansion path
72
Cabinets, 3 pods
$1.5M
Or $20k/mo NNN
Power

What's energized, and what's planned.

The site runs on a real interconnection, not a projection. One transformer is live and serving load today. The second is a planned addition for the step-up to 6 MW — it is not yet on site.

One-line: utility to floor
Utility Feed Pacific Power 2,500 kVA Xfmr ● Online Switchgear & PDU 2.45 MW served 3,750 kVA Xfmr ◌ Planned, not on site 6 MW Target
Contracted capacity in use2.45 MW / 6 MW planned
0 MW
3 MW
6 MW
3 pods · 72 cabinets · ~35 kW/cabinet at 2.45 MW · ~70 kW/cabinet at 6 MW
01

Live today

The 2,500 kVA transformer is installed and operational, serving 2.45 MW of contracted capacity now. No permitting runway required to occupy.

02

Planned for growth

A second, 3,750 kVA transformer is planned but not yet on site. Procurement and installation are part of the step-up to 6 MW.

03

N+1 backup: to be deployed

Natural gas generation at N+1 redundancy is specified and sized for the full 6 MW target, but not yet installed — buildout scope, not standing infrastructure.

Infrastructure

Designed for high-density GPU racks.

The buildout is the next step, not a past one. What follows is the engineering plan for the site — it defines buyer or tenant scope, not equipment already installed.

Buildout required

Cooling

Designed as air-cooled, N+1 inline CDUs feeding glycol-cooled rear-door heat exchangers per cabinet. Not yet installed.

Buildout required

Electrical step-down

Switchgear and PDU deployment down from the 2,500 kVA transformer to the cabinet level is still ahead of occupancy.

Buildout required

N+1 generation

Natural gas backup sized to 6 MW is specified but not installed. Deployment is part of the buyer or tenant scope.

Site

Klamath Falls: power and climate on your side.

High desert elevation and a cool annual climate reduce mechanical cooling load. The site sits on Pacific Power's grid with an active interconnection already in place — not a proposal.

Climate

High-desert cooling

Klamath Falls' elevation and dry climate favor lower mechanical cooling overhead than most coastal or urban colocation markets.

Grid

Pacific Power interconnection

Utility service is active and contracted at 2.45 MW today, with a defined path to 6 MW as demand grows.

Access

Dedicated shell

A standalone data center shell — no shared building systems or unrelated tenants to coordinate around, whether occupied by one tenant or divided among several.

Buildout Plans

Four plans. One shell.

Every plan fits inside the same powered shell. Choose the power ceiling and cooling method that matches your compute, or hold both open through diligence.

Cooling
Air
Cabinets
72
Density
35 kW / cabinet
IT load
~2.52 MW
Layout
4 × 18 pods, 2 rows of 9
Transformer
Existing 2,500 kVA
Estimated buildout cost: $2.66M–$4.01M. Planning-level estimate pending vendor quotes and structural sign-off, not a confirmed cost or lead time.
Cooling
Air
Cabinets
72
Density
80 kW / cabinet
IT load
~5.76 MW
Layout
4 × 18 pods, 2 rows of 9
Transformer
Planned 3,750 kVA
Estimated buildout cost: $3.67M–$5.74M. Generator sizing is an open item at this density — the 2 MW unit on site is undersized and needs re-evaluation. Planning-level estimate, not confirmed.
Cooling
Liquid
Cabinets
16
Density
140 kW / cabinet
IT load
2.24 MW + 200 kW facility
Layout
2 × 8 pods, 2 rows of 4
Transformer
Existing 2,500 kVA
Buildout cost estimate pending vendor quotes. Total facility draw of ~2.44 MW fits inside the existing 2,500 kVA transformer with ~10 kW headroom.
Cooling
Liquid
Cabinets
35
Density
150 kW / cabinet
IT load
5.25 MW + 200 kW facility
Layout
2 × 14 + 1 × 7 pods of 2 rows of 7, plus standalone row
Transformer
Planned 3,750 kVA
Buildout cost estimate pending vendor quotes. Total facility draw of ~5.45 MW leaves ~550 kW of headroom under the 6 MW ceiling.
Terms

Buy the asset, or lease the capacity.

521 Walnut Ave is offered for sale or as a triple-net lease. Both paths start from the live 2.45 MW interconnection; cooling, electrical step-down, and N+1 generation are buildout scope from there.

Purchase
$1,500,000

Acquire the facility outright: land, shell, and the energized 2.45 MW interconnection.

  • 2.45 MW contracted capacity, live
  • Path to a second, 3,750 kVA transformer for 6 MW
  • Cooling and electrical step-down are buyer's scope
Lease
$20,000/mo NNN

Occupy under a triple-net structure; operating expenses pass through.

  • Immediate access to live power
  • Tenant-directed buildout
  • Flexible term, subject to negotiation
521 Walnut Ave is a powered shell. Installed and energized today: the live 2.45 MW Pacific Power interconnection, the 2,500 kVA main transformer, and panel-level step-down transformers. Not yet in place, and scoped as buyer or tenant responsibility: cabinets, cooling infrastructure, and backup generation. Buildout cost figures are planning-level estimates pending vendor quotes, structural sign-off, and utility confirmation. Figures on this page reflect current site conditions as of the date of publication and are subject to change. Contact Jupiter Data directly for current commercial terms.
Inquire

Request the full deal package.

Site plan, one-line diagram, transformer documentation, and the cooling and electrical step-down buildout scope are available on request.